單液位或液位界面,尺寸小,探頭可到6英尺長(1.82 M)
Control Valves, Pumps And Alarms With The Verstile Series LLC Conductivity Level Conroller. Select The Required Number Of Probes For Single Or Dual Point Level Detection. Choose Probe Lengths In 1-Foot Increments (Up To Six Feet) To Adapt The LLC To Your Specific Applications Requirements. The LLC Features Rugged 1/4-Inch (6.3 Mm) Diameter, Stainless Steel Probes, LED Monitoring, Surge Protection, Low Voltage Sensor And Different Mounting Options.
TO BUILD YOUR LEVEL SWITCH:
Controller:
1. Determine Your Supply Voltage. Select Between 120 And 240 VAC.
2. Determine The Required Sensitivity. Select Between 10K Ω And 26K Ω.
3. Determine The Socket Style. Select Between 8-Pin Octal And DIN Mount.
Probes:
4. Determine The Required Number Of Probes. Specify Quantity Of Threaded Mounting Couplings, Model LLC-82. (A Coupling Is Required For Each Probe.)
5. Select Probe Lengths. Specify Model Numbers For Probes.
Service: Electrically Conductive Fluids.
Wetted Materials: 316 Stainless Steel, PTFE.
Temperature Limits: Controller: -40 To 150°F (-40 To 65°C); Probes: 406°F (207°C).
Pressure Limits: Probes: 400 Psig ( 27 Bar).
Accuracy: ±0.25% FS.
Switch Type: SPDT, N.O. Or N.C.
Electrical Rating: 10 Amps Resistive, 1/3 Hp @ 120/240 VAC.
Power Requirements: 120 VAC Or 240 VAC.
Electrodes: 1/4" (6.3 Mm) Diameter, 316 SS.
Maximum Probe Length: 72 Inches (1.82 M).
Controller Sensitivity: 10K Ω Or 26K Ω.
Mounting: Controller: 8 Pin Octal Or DIN Mount; Probes: 3/8" Male NPT.
Weight: Controller: 6 Oz (170 G).